Home | News | Environmental | Products | Services | Contact | Recruitment | Videos | About | CSR | FOREX | Distributors
 

GreaseShield® GS1850-LL-PF

Approvals

ASME A112.14.3-2000 Testing of Grease Interceptors, ASME A112.14.4-2001 Grease Removal Devices, CSA B481.0-2012 Testing of Grease Interceptors, CSA B481.1-2012 Testing and Rating of Grease Interceptors using Lard, CSA B481.5-2012 Testing and Rating of Grease Interceptors Equipped with a Grease Removal Device & PDI G 101. UL Approved (File No: E361705). Machinery Directive 2006/42/EC and EMC directive 2004/108/EC.

Flow Rates

Passive PDI =7GPM/26.5 L/m

Pro Active= 1.8 L/S

Application

10 / 20 Grid Ovens with Low Level Discharge and Sink. Do not exceed rated inflows.

Functions & Features

  • PreFilter
  • Genie H2O Heater On Demand System -Supplied as standard (2509P01)
  • 24 Volt PLC 4 Way - Controls both main and LL tank operation
  • LL Tank Filter built in for LL Inlet - Ensure ovens are plumbed into the LL inlet and sink into the PreFilter inlet
  • Solenoid Valve WRAS approved (or similar approval) Solenoid
  • Anti-Flood Pump - To maintain normal water level + recalibration feature
  • Anti-Flood Sensor included

Parts Supplied as Standard

  • Vortex Flow Controller - Fitted as option on normal inlet.
  • Running Trap – 54mm Running trap fitted on outlet as standard.
  • FlexiPlumb:-54mm Running trap (0635D04-54), 54mm 90° bend (0635P02-54), 40mm 90° bend (0635P02-40) x2, 40mm straight (90635P01), 34mm 90° (0635P02-34)
  • 40mm Blanking Cap (0635D10-40) x2
  • Key (0509P86)
  • Braided Hose For Hot Water (0214P01) x 2 as part of Genie H2O
  • Plumbing Pack-see Note

Default Program

(V1.0 1850-LL)

Start 7.00 Am, Stop 02.30 Am. FOG & Auger pulsing 5 Min On 5 min off. An anti-Flood and Recalibration cycle, when water intake is activated FOG roller is inhibited. Mains lead per country.

Installation Kit

  • Units must be at floor level or located on drop frame castored stands
  • IP56 Socket. Best Practice Management and Do’s and Don'ts, both laminated to be displayed on site.
  • Daily Maintenance Logbook (12 months)
  • Sampling Point

Ratings

  GS1850-LL-PF

Contact Us Now to Discuss Your Effluent Needs Contact Us Now to Discuss Your Effluent Needs Note

RE: Plumbing Pack Water Spray gun and hose for connection to WRAS approved (or similar approval) connection (or equivalent) for service.

Labelling

  • Voltage per country
  • Flow Rate per country
  • Labels per country
  • Labels per Distributor

Average Power Consumption /Hour 23.6 Watts

Notes

  • Plumbing Guidelines to be adhered to IAW Installation and Operation Manual.
  • All FlexiPlumb to be supplied with jubilee clip fasteners
  • VFC= Vortex Flow Controller

UK Installs

AQUACHECK 15DN (WRAS Certified) or equivalent double check valve to be fitted to water supply on ALL GreaseShield® (STD Range Models) to conform with WRAS back flow prevention.

 
 

EU

  • Voltage: 240 Volts
  • Frequency: 50Hz
  • Current: 0.6Amps
 

US

  • Voltage: 120 Volts
  • Frequency: 60Hz
  • Current: 1.2Amps
     
             
  GS1850-LL-PF Dimensional Drawing  
 
AutoCAD Logo Download GS1850-LL-PF AutoCAD File Revit Logo Download GS1850-LL Revit File
 
  The Complete GreaseShield Range          
       
EPAS on Twitter EPAS on Google+ EPAS on LinkedIn Like Us on Facebook